Prerequisites
Sensor: temperature sensor, measuring range –50 to 100 °C
Temperature to be measured 25 °C
Order of events with LOGO!Soft Comfort
The sensor converts the temperature from 25 °C to a voltage value of 5.0 V.
LOGO! converts the 5.0 V to the standardized value 500.
Using the sensor and measurement range data, LOGO! ascertains the value 0.15 for the gain and the value –50 for the offset.
According to the formula:
Analog value = (standardized value x gain) + offset
LOGO! calculates as analog value:
Analog value = (500 x 0.15) - 50 = 25
Order of events with LOGO!
The sensor converts the temperature from 25 °C to a voltage value of 5.0 V.
LOGO! converts the 5.0 V to the standardized value 500.
From the sensor and measuring range data you must establish the values for gain and offset.
According to the formulas:
Gain = (maxSensor – minSensor) / (maxnorm – minnorm)
and
Offset = minSensor – (Gain x minnorm)
it follows that
Gain = (100 – (-50)) / (1000 – 0) = 0.15
Offset = -50 – (0.15 x 0) = -50
According to the formula
Analog value = (standardized value x gain) + offset
LOGO! calculates as analog value:
Analog value = (500 x 0.15) - 50 = 25
Additional examples
Physical quantity | Electric quantity of sensor | Standardized value | Gain | Offset | Analog value |
|---|---|---|---|---|---|
0 V 5 V 10 V | 0 500 1000 | 0.01 | 0 | 0 5 10 | |
4 mA 12 mA 20mA | 0 500 1000 | 10 | 0 | 0 5000 10000 | |
0 mA 10 mA 20 mA | 0 500 1000 | 1 | 50 | 50 550 1050 | |
1000 mbar 3700 mbar 5000 mbar | O V 6.75 V 10 V | 0 675 1000 | 4 | 1000 | 1000 3700 5000 |
-30 °C 0 °C 70 °C | 0 mA 6 mA 20 mA | 0 300 1000 | 0.1 | -30 | -30 0 70 |